    Calibration of a 3 MV LI measuring system by comparison method and by numerical convolution using its measured step response

  • Author

    Breilmann, W. ; Haupt, H.

  • Author_Institution
    Darmstadt Univ. of Technol., Germany
  • Volume
    1
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    230
  • Abstract
    The dynamic errors of peak value uˆ, front time T1 and time to half value T2 of an approved 3 MV LI (lightning impulse) measuring system were experimentally determined for two standard LIs with uˆ=500 kV, T1=1.2 μs±20% and T2=60 μs by two different methods. The first method is according to the comparison of an Approved Measuring System with a 500 kV Reference Measuring System. The second method is the convolution of the normalized step response g(t) of the 3 MV system with the standard LI input voltage measured with the Reference Measuring System. Agreement within 0.5% for uˆ and within 1.2% for T1 and T2 was achieved
  • Keywords
    voltage measurement; 3 MV; 500 kV; Approved Measuring System; Reference Measuring System; calibration; lightning impulse measuring system; normalized step response;