DocumentCode :
3516664
Title :
High Current Arc Erosion on Copper Electrodes in Air
Author :
Øyvang, T. ; Fjeld, Elin ; Rondeel, Wilhelm ; Hagen, Svein Thore
Author_Institution :
Fac. of Technol., Telemark Univ. Coll., Porsgrunn, Norway
fYear :
2011
fDate :
11-14 Sept. 2011
Firstpage :
1
Lastpage :
6
Abstract :
An arc fault inside metal enclosed switchgear will cause the pressure to rise and vaporization of electrode material may contribute to the pressure rise. An experimental study of high current arc erosion on copper electrodes in air has been performed, with an evaluation of fraction lost by gross melting and vaporization. All experiments were performed at NEFI High Voltage Laboratory in Skien, Norway. The measured mass loss from vaporization in our experiments seems to be negligible compared to erosion by gross melting.
Keywords :
arcs (electric); electrical faults; electrodes; switchgear; NEFI High Voltage Laboratory; arc fault; copper electrode; electrode material vaporization; fraction lost evaluation; gross melting; high current arc erosion; mass loss measurement; metal enclosed switchgear; Copper; Current measurement; Electrodes; Fingers; Loss measurement; Materials;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Contacts (Holm), 2011 IEEE 57th Holm Conference on
Conference_Location :
Minneapolis, MN
ISSN :
1062-6808
Print_ISBN :
978-1-61284-650-7
Type :
conf
DOI :
10.1109/HOLM.2011.6034779
Filename :
6034779
Link To Document :