DocumentCode :
3526565
Title :
Partial discharge measurements in a high temperature superconducting triaxial 5-m model cable at liquid nitrogen temperature
Author :
Sauers, I. ; James, D.R. ; Tuncer, E. ; Ellis, A. ; Pace, M.O.
Author_Institution :
Oak Ridge Nat. Lab., TN
fYear :
2006
fDate :
15-18 Oct. 2006
Firstpage :
664
Lastpage :
667
Abstract :
A prototype 5-m triaxial high temperature superconducting (HTS) distribution class cable using a cold dielectric design was tested at high voltage under various conditions including AC, impulse and partial discharge (PD). The dielectric consists of wrapped synthetic tape insulation with liquid nitrogen filling the butt-gaps. In this paper we report on the partial discharge signals in the cable and methods for data analysis. All measurements were made cold in liquid nitrogen. The data will be presented in terms of PD amplitude and energy. Partial discharge signals were observed in the presence of large amounts of background noise due to the inverter circuits of the cryogenic system and these issues will also be discussed.
Keywords :
partial discharges; power cables; superconducting cables; AC discharge; cold dielectric design; cryogenic system; high temperature superconducting triaxial cable; impulse discharge; inverter circuits; liquid nitrogen temperature; partial discharge signals; synthetic tape insulation; Dielectric liquids; High temperature superconductors; Nitrogen; Partial discharge measurement; Partial discharges; Power cable insulation; Power cables; Prototypes; Superconducting cables; Superconducting films;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2006 IEEE Conference on
Conference_Location :
Kansas City, MO
Print_ISBN :
1-4244-0547-5
Electronic_ISBN :
1-4244-0547-5
Type :
conf
DOI :
10.1109/CEIDP.2006.312019