• DocumentCode
    3535346
  • Title

    Experimental evaluation of damper circuit influence on the performance of multiphase synchrnounous generators feeding multiple rectifiers

  • Author

    Mezzarobba, Mario ; Spangaro, Luca ; Tessarolo, Alberto

  • Author_Institution
    Electr. Eng. Dept., Univ. of Trieste, Trieste, Italy
  • fYear
    2011
  • fDate
    11-13 May 2011
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    In today´s power generation systems, driven by variable-speed prime movers and feeding DC or fixed-frequency grids, the output power of the alternator needs to be rectified. The presence of output rectifier bridges causes a significant distortion of phase currents. This paper investigates the role played by rotor damper circuits in limiting the effects of such distortion. The investigation is extended to the case of multiphase alternator arrangements suitable for supplying a different number of output rectifiers. The study is conducted through tests on an alternator prototype which has been operated with two kinds of rotors, one with and the other without damper circuits. Testing results show that the influence of dampers is significant only in the case of generator three-phase winding and single output bridge.
  • Keywords
    alternators; damping; distortion; machine windings; power grids; rectifiers; rotors; variable speed drives; alternator; fixed-frequency grids; multiphase synchronous generators; phase current distortion; power generation systems; rectifiers; rotor damper circuits; three-phase winding; variable-speed prime movers; Alternators; Bridge circuits; Generators; Rectifiers; Rotors; Shock absorbers; Stators; Damper circuits; Multiphase; Power generation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering, Energy and Electrical Drives (POWERENG), 2011 International Conference on
  • Conference_Location
    Malaga
  • ISSN
    2155-5516
  • Print_ISBN
    978-1-4244-9845-1
  • Electronic_ISBN
    2155-5516
  • Type

    conf

  • DOI
    10.1109/PowerEng.2011.6036541
  • Filename
    6036541