DocumentCode :
3535571
Title :
Motor starting study for a urea manufacturing plant
Author :
Abbas, Mohammed ; Majeed, M. Arif Abdul ; Kassas, M. ; Ahmad, F.
Author_Institution :
King Fahd Univ. of Pet. & Miner. (KFUPM), Dhahran, Saudi Arabia
fYear :
2011
fDate :
11-13 May 2011
Firstpage :
1
Lastpage :
6
Abstract :
Dynamic and static starting motor starting studies were conducted for the largest motor (13.2 kV, 3200kW) in a Saudi-based urea manufacturing plant for peak load and worst case scenarios. The results of these motor simulation studies indicate no motor starting problems in the peak load scenario. Motor starting in the worst case plant operating conditions however was found to cause significant voltage dips that can affect plant operation. Based on the motor starting simulation results, the necessary remedial measures are suggested for ensuring trouble-free plant operation in worst case conditions.
Keywords :
fertilisers; induction motors; power supply quality; starting; Saudi-based urea manufacturing plant; dynamic starting; motor simulation study; motor starting; peak load scenario; static starting; trouble-free plant operation; voltage dip; worst case scenario; Induction motors; Power quality; Substations; Synchronous motors; Torque; Voltage fluctuations; Direct-on-line; Dynamic Motor Simulation; Induction Motor starting; Modeling; Motor Acceleration Time; Power Transformers; Tap Adjustment; Voltage Sag;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering, Energy and Electrical Drives (POWERENG), 2011 International Conference on
Conference_Location :
Malaga
ISSN :
2155-5516
Print_ISBN :
978-1-4244-9845-1
Electronic_ISBN :
2155-5516
Type :
conf
DOI :
10.1109/PowerEng.2011.6036562
Filename :
6036562
Link To Document :