Study on the over-current protection method of the large power inverter with IGCTs
Author
Wang Chengsheng ; Li Chongjian ; Zhu Chuyi ; Lan Zhiming ; Yang Qiongtao ; Duan Wei ; Li Fan
Author_Institution
Hybrid Process Ind. Autom. Syst. & Equip. Technol. State Key Lab., Autom. Res. & Design Inst. of Metall. Ind., Beijing, China
fYear
2013
fDate
2-6 Sept. 2013
Firstpage
1
Lastpage
7
Abstract
Large power three-level voltage source inverters with IGCTs are widely used in medium and large power drive systems now and have prospective future. Measures should be carefully taken to protect the inverter when over-current occurs due to every reason, especially that due to short circuit in the load or in the inverter itself. The short circuit process of the inverter with IGCTs is analyzed. With software simulation and experiment, the influence of some circuit parameters on the short circuit process is investigated. Then the schematic diagram of the inverter with over-current protection function is designed. System experiments show the inverter has excellent performance.
Keywords
electric drives; invertors; IGCT; circuit parameter; inverter schematic diagram; large-power drive systems; large-power three-level voltage source inverters; medium-power drive systems; over-current protection method; power inverter; short-circuit process; software simulation; Capacitors; Discharges (electric); Integrated circuit modeling; Inverters; Load modeling; Resistors; Surges; IGCT; inverter; large power; over-current; protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics and Applications (EPE), 2013 15th European Conference on
Conference_Location
Lille
Type
conf
DOI
10.1109/EPE.2013.6631940
Filename
6631940
Link To Document