• DocumentCode
    3544429
  • Title

    Research on the over-voltage of 220kV power system caused by traction transformer´s commissioning

  • Author

    Fangxiao, Cheng ; Ying, Sun ; Weiping, Ma

  • Author_Institution
    Changchun Univ. of Technol., Changchun, China
  • fYear
    2009
  • fDate
    16-19 Aug. 2009
  • Abstract
    The over-voltage of 220 kV power system appeared during the commissioning of several traction transformers in Jilin Province. Analysis showed that the electromagnetic oscillating of the system caused the over-voltage of the feeding phases. After setting up an accurate simulating model used in ATP-EMTP, the adverse influence on the electric power system and the character of the oscillation over-voltage had been studied. Results showed that under the environment of these substations the amplitude of the over-voltage couldn´t exceed 2.0 p.u and would have little influence on electric power system.
  • Keywords
    EMTP; overvoltage protection; power system analysis computing; power system transients; power transformers; substations; traction; ATP-EMTP; Jilin Province; alternative transients program; electric power system; electromagnetic oscillating; power system over-voltage; substations; traction transformer commissioning; voltage 220 kV; Frequency; Power system modeling; Power system simulation; Power system transients; Power systems; Power transmission lines; Rail transportation; Substations; System testing; Transformers; Oscillating over-voltage Transformer Simulating study;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electronic Measurement & Instruments, 2009. ICEMI '09. 9th International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-3863-1
  • Electronic_ISBN
    978-1-4244-3864-8
  • Type

    conf

  • DOI
    10.1109/ICEMI.2009.5274507
  • Filename
    5274507