DocumentCode
3550077
Title
Numerical simulation and parameter identification of the temperature field in the oil-immersed self cooled three phrase transformer
Author
Enmin Feng ; Zhengyan Guo
Volume
3
fYear
2004
fDate
6-9 Dec. 2004
Firstpage
2165
Abstract
In view of the non-steady of temperature field in the large oil-immersed self-cooled three-phrase transformer, this paper constructs parameter identification model and make the numerical simulation. Due to the nonsmooth property of the temperature field of the transformer, the overlapping domain decomposition method is employed to make the coil under the cylindrical coordinate, and the core limb, the yoke and the oil out of the coil under the rectangular coordinate. The interface conditions among subdomains are given. Finally the optimal algorithm is proposed to solve the parameter identification problem and the corresponding software is made. The comparison of experimental data and numerical results shows the correctness and efficiency of our methods.
Keywords
difference equations; parameter estimation; temperature control; transformers; domain decomposition method; numerical simulation; oil-immersed self cooled three phrase transformer; parameter identification; temperature field; Coils; Differential equations; Finite element methods; Mathematics; Numerical simulation; Oil insulation; Parameter estimation; Petroleum; Temperature; Transformer cores;
fLanguage
English
Publisher
ieee
Conference_Titel
Control, Automation, Robotics and Vision Conference, 2004. ICARCV 2004 8th
Print_ISBN
0-7803-8653-1
Type
conf
DOI
10.1109/ICARCV.2004.1469500
Filename
1469500
Link To Document