DocumentCode
3558880
Title
Line Outage Detection Using Phasor Angle Measurements
Author
Tate, Joseph Euzebe ; Overbye, Thomas J.
Author_Institution
Dept. of Electr. & Comput. Eng., Toronto Univ., Toronto, ON
Volume
23
Issue
4
fYear
2008
Firstpage
1644
Lastpage
1652
Abstract
Although phasor measurement units (PMUs) have become increasingly widespread throughout power networks, the buses monitored by PMUs still constitute a very small percentage of the total number of system buses. Our research explores methods to derive useful information from PMU data in spite of this limited coverage. In particular, we have developed an algorithm which uses known system topology information, together with PMU phasor angle measurements, to detect system line outages. In addition to determining the outaged line, the algorithm also provides an estimate of the pre-outage flow on the outaged line. To demonstrate the effectiveness of our approach, the algorithm is demonstrated using simulated and real PMU data from two systems - a 37-bus study case and the TVA control area.
Keywords
phase measurement; power system faults; power system measurement; PMU data; line outage detection; phasor angle measurement; phasor measurement units; power networks; power system; pre-outage flow; Goniometers; Network topology; Phasor measurement units; Power grids; Power measurement; Power system dynamics; Power system measurements; Power system reliability; Power system simulation; State estimation; Event detection; line outages; phasor measurement units;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2008.2004826
Filename
4652583
Link To Document