• DocumentCode
    3558880
  • Title

    Line Outage Detection Using Phasor Angle Measurements

  • Author

    Tate, Joseph Euzebe ; Overbye, Thomas J.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Toronto Univ., Toronto, ON
  • Volume
    23
  • Issue
    4
  • fYear
    2008
  • Firstpage
    1644
  • Lastpage
    1652
  • Abstract
    Although phasor measurement units (PMUs) have become increasingly widespread throughout power networks, the buses monitored by PMUs still constitute a very small percentage of the total number of system buses. Our research explores methods to derive useful information from PMU data in spite of this limited coverage. In particular, we have developed an algorithm which uses known system topology information, together with PMU phasor angle measurements, to detect system line outages. In addition to determining the outaged line, the algorithm also provides an estimate of the pre-outage flow on the outaged line. To demonstrate the effectiveness of our approach, the algorithm is demonstrated using simulated and real PMU data from two systems - a 37-bus study case and the TVA control area.
  • Keywords
    phase measurement; power system faults; power system measurement; PMU data; line outage detection; phasor angle measurement; phasor measurement units; power networks; power system; pre-outage flow; Goniometers; Network topology; Phasor measurement units; Power grids; Power measurement; Power system dynamics; Power system measurements; Power system reliability; Power system simulation; State estimation; Event detection; line outages; phasor measurement units;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2008.2004826
  • Filename
    4652583