• DocumentCode
    3559326
  • Title

    On the Mechanical Short-Time Rating of a Current Transformer

  • Author

    Gopalakrishna, S. ; Ilampoornan, M.K. ; Jayashankar, V.

  • Author_Institution
    Dept. of Electr. Eng., Indian Inst. of Technol. Madras, Chennai
  • Volume
    24
  • Issue
    1
  • fYear
    2009
  • Firstpage
    480
  • Lastpage
    481
  • Abstract
    Closed-form expressions and a finite-element method are used to compute the maximum force in the primary conductor of a wound current transformer (CT). It is shown that for a given volume for the primary winding, one configuration exists that leads to a maximum force. It is proved that the mechanical short-time rating of two CTs having different turns but identical ampere turns is not equivalent. Designers can now establish and test a CT with a worst-case configuration.
  • Keywords
    finite element analysis; power transformers; closed-form expressions; finite-element method; mechanical short-time rating; worst-case configuration; wound current transformer; Current transformer (CT); finite-element method (FEM); short-time rating;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • Conference_Location
    12/9/2008 12:00:00 AM
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2008.2007008
  • Filename
    4703205