DocumentCode
3559326
Title
On the Mechanical Short-Time Rating of a Current Transformer
Author
Gopalakrishna, S. ; Ilampoornan, M.K. ; Jayashankar, V.
Author_Institution
Dept. of Electr. Eng., Indian Inst. of Technol. Madras, Chennai
Volume
24
Issue
1
fYear
2009
Firstpage
480
Lastpage
481
Abstract
Closed-form expressions and a finite-element method are used to compute the maximum force in the primary conductor of a wound current transformer (CT). It is shown that for a given volume for the primary winding, one configuration exists that leads to a maximum force. It is proved that the mechanical short-time rating of two CTs having different turns but identical ampere turns is not equivalent. Designers can now establish and test a CT with a worst-case configuration.
Keywords
finite element analysis; power transformers; closed-form expressions; finite-element method; mechanical short-time rating; worst-case configuration; wound current transformer; Current transformer (CT); finite-element method (FEM); short-time rating;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
Conference_Location
12/9/2008 12:00:00 AM
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2008.2007008
Filename
4703205
Link To Document