DocumentCode
3559821
Title
Ultra-wide-band PD diagnostics of power cable terminations in service
Author
Lemke, Eberhard ; Strehl, Thomas ; Markalous, Sacha ; Weissenberg, Werner
Author_Institution
LDIC GmbH, Kesselsdorf
Volume
15
Issue
6
fYear
2008
fDate
12/1/2008 12:00:00 AM
Firstpage
1570
Lastpage
1575
Abstract
During the past decade the PD probing in the ultra-high frequency (UHF) range has successfully been proven for on-site PD diagnostics of GIS cable terminations in service. Therefore it was decided to apply this non-conventional method also for condition assessment of the insulation integrity of outdoor cable terminations. In order to evaluate the minimum detectable PD level the paper deals with comparative PD studies using the IEC and the UHF method. Moreover, experimental studies on the attenuation of PD pulses traveling through power cables were performed in order to assess the spatial selectivity of the UHF method applied.
Keywords
gas insulated switchgear; partial discharges; power cable insulation; GIS cable terminations; condition assessment; insulation integrity; power cable terminations; ultra-high frequency range; ultra-wide-band partial discharge diagnostics; Frequency measurement; Geographic Information Systems; IEC standards; Power cables; Power transformer insulation; Pulse measurements; Pulse transformers; Testing; UHF measurements; Ultra wideband technology;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
Conference_Location
12/1/2008 12:00:00 AM
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2008.4712659
Filename
4712659
Link To Document