DocumentCode
3559822
Title
Detection and location of partial discharges in power transformers using acoustic and electromagnetic signals
Author
Markalous, Sacha M. ; Tenbohlen, Stefan ; Feser, Kurt
Author_Institution
LDIC GmbH, Kesselsdorf
Volume
15
Issue
6
fYear
2008
fDate
12/1/2008 12:00:00 AM
Firstpage
1576
Lastpage
1583
Abstract
The measurement of partial discharges (PD) is a non-destructive and sensitive diagnostic tool for the condition assessment of insulating systems. Two major tasks of PD measurements may be distinguished, (i) PD detection, hence providing evidence and the type of the PD and (ii) the location of the PD. The question "Where is the PD source?" is amongst others tremendously important for scheduling and starting maintenance/repair actions cost and time efficiently or to perform a risk analysis. Here the possibility to geometrically localize the flaw, by means of arrival times of acoustic PD signals, gets an extremely interesting option. Precise acoustic arrival times are consequently essential to accurately locate PD in a power transformer. The averaging of acoustic PD signals helps to enhance the acoustic sensitivity. The acoustic detection limit is lowered significantly and the determination of the arrival times is made possible for weaker PD. Supplementary steps, like automatic objective arrival time determination or additional wavelet-based de-noising further improve the overall location accuracy. A new location approach works with pseudo-times and allows for the use of robust direct solvers instead of the previously used iterative algorithms.
Keywords
UHF measurement; acoustic measurement; flaw detection; insulation testing; maintenance engineering; partial discharge measurement; power transformer insulation; power transformer testing; risk analysis; time-of-arrival estimation; PD measurement; acoustic sensitivity; acoustic signals; additional wavelet-based denoising; electromagnetic signals; flaw localization; insulating system; nondestructive diagnostic tool; partial discharge detection; partial discharge location; power transformers; risk analysis; time-of-arrival; Acoustic measurements; Acoustic signal detection; Acoustic waves; Costs; Electromagnetic measurements; Noise reduction; Partial discharges; Power transformer insulation; Power transformers; Risk analysis; PD location, electromagnetic (UHF) and acoustic PD measurements, de-noising, wavelet, acoustic averaging, arrival time determination;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
Conference_Location
12/1/2008 12:00:00 AM
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2008.4712660
Filename
4712660
Link To Document