Robustness of distance relay with Mho characteristic against fault resistance
Author
Jamali, S. ; Shateri, H.
Author_Institution
Iran Univ. of Sci. & Technol., Tehran, Iran
Volume
2
fYear
2004
Firstpage
679
Abstract
This paper discusses the maximum earth fault resistance which can be tolerated by a distance relay with Mho characteristic. This is defined as the boundary fault resistance the relay can discriminate between in-zone and out-of-zone faults. The robustness criterion is defined on the basis of the boundary fault resistance. In order to achieve this, the related equations are first derived and then the boundary fault resistance curve is presented. The simulation results for a typical transmission system shows the effectiveness of the proposed robustness criterion for distance relay settings.
Keywords
earthing; power system faults; power system protection; power system simulation; relay protection; robust control; Mho characteristic; boundary fault resistance; boundary fault resistance curve; distance relay; fault resistance; in-zone faults; maximum earth fault resistance; out-of-zone faults; robustness; simulation; Circuit faults; Earth; Electrical resistance measurement; Impedance; Power system faults; Power system protection; Power system relaying; Protective relaying; Relays; Robustness;