DocumentCode
3565777
Title
The induced overvoltage between UHV AC and DC transmission lines built on the same tower under fault conditions
Author
Sun, Qiuqin ; Shi, Wei ; Siew, W.H. ; Liu, Hongshun ; Li, Qingmin
Author_Institution
ShanDong Univ., Jinan, China
fYear
2009
Firstpage
1
Lastpage
5
Abstract
Rapid increase of the transmission capacity and environmental limit of the power transmission passage have indispensably promoted development of the AC/DC hybrid transmission lines on the same tower, especially for UHV systems being established in China. Unfortunately, severe electromagnetic coupling effects will inevitably exist between the UHV AC and DC transmission lines built on the same tower. The generating mechanisms, as well as the computational methodology, of both the inductive and capacitive coupling effects within the hybrid transmission lines are elucidated in the paper, then an equivalent circuitry model is established as to analyze the induced overvoltage within the hybrid transmission lines under different fault conditions. Further, the impacts on the induced overvoltage on the healthy line from key influential factors, such as the grounding fault resistance, the collocation and layout of DC filters and fault type, are accounted for in details. Specifically, phase-mode transform method is adopted to theoretically analyze the effect of transposition mode of the UHV AC transmission line as how to reduce the induced overvoltage within the hybrid transmission lines. The proposed method and analyzed results present reliable reference for realizing optimal design of the UHV AC/DC hybrid transmission lines.
Keywords
HVDC power transmission; earthing; fault diagnosis; poles and towers; AC-DC hybrid transmission lines; DC filters; UHV AC transmission lines; UHV DC transmission lines; capacitive coupling effects; fault conditions; grounding fault resistance; inductive coupling effects; phase-mode transform method; tower; transposition mode; Circuit faults; Distributed parameter circuits; Electromagnetic coupling; Hybrid power systems; Poles and towers; Power transmission; Power transmission lines; Transmission line theory; Transmission lines; Voltage control; AC/DC Hybrid Transmission; Fault; Induced Overvoltage; Transposition Mode; UHV;
fLanguage
English
Publisher
ieee
Conference_Titel
Universities Power Engineering Conference (UPEC), 2009 Proceedings of the 44th International
Print_ISBN
978-1-4244-6823-2
Type
conf
Filename
5429371
Link To Document