DocumentCode :
3568903
Title :
Interference monitoring during the factory PD tests of ±800kV converter transformer
Author :
Bo Qi ; Zongwang Zhu ; Hongxin Ji ; Chengrong Li ; Linjie Zhao ; Ruihai Li
Author_Institution :
State Key Lab. of Alternate Electr. Power, North China Electr. Power Univ., Beijing, China
fYear :
2015
Firstpage :
270
Lastpage :
273
Abstract :
Partial discharge (PD) level under the specified AC/DC test voltages, which is one key parameter indicating the insulation reliability of ultra-high voltage direct current (UHVDC) converter transformers, do not often be accurately determined due to the impact of the external electromagnetic interference. To solve this problem, a method that uses the ultra-high frequency (UHF) technology to monitor the PD interferences was brought forward in this paper, and was applied to the factory tests of a ± 800kV converter transformer. The results show that the waveform characteristic of the UHF detection signals can be well used for recognizing the interferences caused by communication equipment, as well as the phase distribution characteristics of the UHF detection signals for the floating potential discharge and the point discharge induced by various types of AC / DC test voltages. The results also confirm that the floating discharge spots and the point discharge spots can be quickly and accurately located by analyzing the arriving time difference of RF signals at the different sensors of the UHF antenna array. Based on the monitoring results, the PD interference sources were well treated and then the ± 800kV converter transformer smoothly passed the partial discharge measurements. The research results will be further deployed to the similar work of the UHVDC converter transformers in the converter stations.
Keywords :
HVDC power convertors; UHF antennas; UHF detectors; electromagnetic interference; partial discharge measurement; power system faults; power system measurement; power system reliability; power transformer insulation; AC-DC test voltages; PD test; RF signals; UHF antenna array; UHF detection signals; UHF technology; UHVDC; electromagnetic interference; floating discharge; interference monitoring; partial discharge measurements; point discharge; ultra-high frequency technology; ultrahigh voltage direct current converter transformers insulation reliability; voltage 800 kV; Discharges (electric); Frequency measurement; Monitoring; Partial discharges; Power measurement; Power systems; UHF; converter transformer; interference; location; partial discharge;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference (EIC), 2015 IEEE
Print_ISBN :
978-1-4799-7352-1
Type :
conf
DOI :
10.1109/ICACACT.2014.7223484
Filename :
7223484
Link To Document :
بازگشت