DocumentCode
3574378
Title
Effective optimal placement of PMUs for power system observability
Author
Kumar, K. Satish ; Sydulu, Maheswarapu
Author_Institution
Nat. Inst. of Technol., Warangal, India
fYear
2014
Firstpage
119
Lastpage
123
Abstract
This paper presents a new algorithm for optimal placement of PMU\´s to make the given power system network observable under normal operating conditions. Observability test is carried out based on topological connectivity of network, using "root vector" without any need for triangularisation of a matrix. The root vector indicates the number of buses observed due to the placement of PMU at a bus. The aim of the optimal PMU placement problem is to minimize the number of PMU\´s employed in the power system to make it observable. The proposed technique is tested on IEEE 14-bus and 30-bus systems. Further, this technique is also tested on partial network of Southern Grid of India. The test results are compared with the existing algorithms and the results of the proposed algorithm are very promising with significant reduction in CPU time. Therefore, evidently this algorithm can be employed very effectively for well grown large size power systems for optimal placement of PMU\´s.
Keywords
network topology; phasor measurement; power grids; CPU time; IEEE 14-bus system; IEEE 30-bus system; Southern Grid of India; optimal PMU placement problem; partial network; phasor measurement unit; power system observability; root vector; topological network connectivity; Conferences; Observability; Phasor measurement units; Power measurement; Power system stability; Vectors; ADJQ; ITAGF; ITAGTO; NLCONT; Observability analysis; part of South Grid Of India; phasor measurement units;
fLanguage
English
Publisher
ieee
Conference_Titel
Circuit, Power and Computing Technologies (ICCPCT), 2014 International Conference on
Print_ISBN
978-1-4799-2395-3
Type
conf
DOI
10.1109/ICCPCT.2014.7054934
Filename
7054934
Link To Document