Title :
Proposed standards for frequency conversion factors of transformer performance parameters
Author :
Girgis, Ramsis S. ; Beaster, Barry ; TeNyenhuis, Ed G.
Author_Institution :
ABB Power T&D Co. Inc., St. Louis, MO, USA
fDate :
6/23/1905 12:00:00 AM
Abstract :
This paper presents the development of appropriate frequency conversion factors for performance parameters of transformers. These factors are needed in order to allow manufacturers to convert measured values from 60 Hz to 50 Hz and vice versa. Conversion factors are necessary when equipment at a manufacturer´s test facility allows direct measurement at one frequency and not the other. These factors are developed in this paper for no load loss, exciting current, load loss, and noise level using both analytical and actual tested data. Measured data, provided by several manufacturers, was used to confirm the theoretical results. This paper will be used as a basis for proposing standard frequency conversion factors in the IEEE/ANSI and IEC test standards for power and distribution transformers. Such a standard will make it possible for manufacturers to use the same frequency conversion factors and hence have a more uniform accuracy of the reported test data at both 50 and 60 Hz
Keywords :
IEC standards; IEEE standards; measurement standards; power transformer testing; 50 Hz; 60 Hz; IEC test standards; IEEE/ANSI test standards; distribution transformers; exciting current; frequency conversion factors standards; load loss; no load loss; noise level; power transformer performance parameters; test facility; ANSI standards; Frequency conversion; Frequency measurement; IEC standards; Magnetic materials; Manufacturing; Noise level; Power transformers; Testing; USA Councils;
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2001 IEEE/PES
Print_ISBN :
0-7803-7285-9
DOI :
10.1109/TDC.2001.971226