• DocumentCode
    3579062
  • Title

    An integrated impedance based pilot protection scheme for SVC compensated transmission line

  • Author

    Gupta, Om Hari ; Tripathy, Manoj

  • Author_Institution
    Electr. Eng. Dept., Indian Inst. of Technol. Roorkee, Roorkee, India
  • fYear
    2014
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper presents a fault detection and classification scheme, based on integrated impedance, for SVC compensated transmission line. For internal faults, integrated impedance of faulty phase is low and for healthy phase, it is high. For all external faults, integrated impedances of all phases are high. The protection scheme based on this concept is used for variable impedance shunt compensation (i.e. Static Var Compensator, SVC). Proposed scheme has been analyzed for each phase with different fault resistances, fault types and fault locations. The results demonstrate the effectiveness of the proposed scheme.
  • Keywords
    electric impedance; fault location; power transmission faults; power transmission lines; power transmission protection; static VAr compensators; SVC compensated transmission line; fault classification; fault detection; fault location; fault resistance; faulty phase; impedance shunt compensation; integrated impedance based pilot protection scheme; static VAr compensator; Circuit faults; Fault location; Impedance; Power transmission lines; Relays; Resistance; Static VAr compensators; Fault classification; SVC; integrated impedance; pilot relaying; protection of compensated line;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power, Control and Embedded Systems (ICPCES), 2014 International Conference on
  • Print_ISBN
    978-1-4799-5910-5
  • Type

    conf

  • DOI
    10.1109/ICPCES.2014.7062798
  • Filename
    7062798