• DocumentCode
    357915
  • Title

    The first dual-purpose lab for 35 KV epoxy transformer in China

  • Author

    Ying San Yn ; Chen, You-Qing ; Wang, Li-Jun ; Xie, Min Qiang ; Zhu, Mao-Lin ; Yan, Shu-Ning ; Fang, Zuo-Yi ; Luo, Jiang-Ping ; Peng, Fang-Ju

  • Author_Institution
    China Shun-De Electr. Co., China
  • Volume
    1
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    151
  • Abstract
    A new lab for PD/sound level measurement used to 35 kV epoxy transformer has been created in Guang-Dong China. The background sound level of the Lab<25 dBA while it is 80 dBA in ambient, the noise level for PD test<1 pC, the max. capacity and max. weight of tested transformer for sound level and PD detection are 2.5 MVA and 4.0 MVA, 8.8T, and 12T respectively
  • Keywords
    epoxy insulation; insulation testing; laboratories; partial discharge measurement; power transformer insulation; power transformer testing; 35 kV; China; EM shielded room; PD measurement; dual-purpose laboratory; epoxy insulation; noise elimination room; power transformer; sound level measurement; Acoustic noise; Acoustic testing; Background noise; Circuit testing; Level measurement; Noise level; Partial discharges; Power transformer insulation; Steel; System testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 2000. Proceedings of the 6th International Conference on
  • Conference_Location
    Xi´an
  • Print_ISBN
    0-7803-5459-1
  • Type

    conf

  • DOI
    10.1109/ICPADM.2000.875652
  • Filename
    875652