    Methodology to differentiate type of single-phase line break fault in 10kV ungrounded distribution networks

  • Author

    Fangfang Shi ; Wei Cong

  • Author_Institution
    Key Lab. of Power Syst. Intell. Dispatch & Control of Minist. of Educ., Shandong Univ., Jinan, China
  • fYear
    2014
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    10kV distribution network is always a neutral point ungrounded system. Single-phase line break and grounding fault frequently occurs in 10kV distribution networks, threats the safe and stable operation of power grid and damages people´s lives and properties. A methodology to differentiate type of single-phase line break fault is proposed in this paper, which uses sequence network and symmetrical components method to analyze and summarize the voltage and current variation when various single-phase line break fault occurs, then draw the voltage phasor diagram and current phasor diagram. The voltage and current variation and phasor diagrams will provide criteria for the detection and identification of single-phase line break fault in ungrounded distribution networks. Simulation results show the accuracy of the theoretical analysis in this paper.
  • Keywords
    earthing; power distribution faults; power distribution protection; power grids; current phasor diagram; distribution networks; grounding fault; neutral point ungrounded system; power grid; single-phase line break fault; voltage 10 kV; voltage phasor diagram; Circuit faults; Grounding; Impedance; Ports (Computers); Power supplies; Simulation; distribution network; phasor diagram; sequence network; single-phase line break fault;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2014 IEEE PES Asia-Pacific
  • Type

    conf

  • DOI
    10.1109/APPEEC.2014.7066042
  • Filename
    7066042