DocumentCode
3581156
Title
Solution for high temperature slip ring problem of the generators in Guangzhou pumped storage power station phase I
Author
Huang Wei ; Lo, Patrick
Author_Institution
Maintenance Centre Guangzhou Pumped Storage Power Station Power Generation Co., China Southern Power Grid, Guangzhou, China
fYear
2014
Firstpage
1
Lastpage
5
Abstract
Guangzhou Pumped Storage Power Station (GPSPS) plays an important role as the main peaking plant to sustain safe and reliable power supply in the network system. However, some problems existed in the turbine generator from time to time affected the reliability and availability of generating unit. This paper aims to share experience to solve the high temperature problem of generator slip ring of the GPSPS generating units. The key issue was that the operating temperature of generator slip ring was too high during operation. The root cause of problem was mainly due to the inadequate design of construction arrangement and ventilation of the slip rings. In light of cost effectiveness and simplicity, replacement of carbon brush with new design model was the most feasible solution to resolve the high temperature problem of slip ring. This experience sharing could also serve to provide reference to other generators having the same problem of generator slip rings in the stations.
Keywords
power generation reliability; power supply quality; pumped-storage power stations; slip (asynchronous machines); turbogenerators; GPSPS generating unit reliability; Guangzhou pumped storage power station; carbon brush replacement; power supply reliability; turbine generator slip ring problem; Brushes; Carbon; Contact resistance; Films; Friction; Generators; Ventilation; Slip ring; pumped storage power station; turbine generator unit;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2014 IEEE PES Asia-Pacific
Type
conf
DOI
10.1109/APPEEC.2014.7066172