• DocumentCode
    3581421
  • Title

    Thermal ageing and corrosive sulphur effect on partial discharge and electrical conductivity of oil impregnated paper

  • Author

    Bramantyo, A.P. ; Suwarno ; Serra, S. ; Cavallini, A. ; Montanari, G.C.

  • Author_Institution
    PT. PLN (Persero), Persero, Indonesia
  • fYear
    2014
  • Firstpage
    163
  • Lastpage
    166
  • Abstract
    Corrosive sulphur has been identified as the cause of numerous failures of relatively new transformers. In this paper, models of transformer turn insulation were put into artificially-contaminated (315 ppm of DBDS) mineral oil. The ageing procedure consisted of thermal cycles with maximum temperature of 140°C. Between cycles, partial discharges were measured and processed in order to extract diagnostic markers able to highlight copper sulphide contamination. In particular, attention was paid to identify specific PD patterns associated with this type of degradation. Other additional tests, such as electrical conductivity measurements, were also performed.
  • Keywords
    contamination; corrosion; electrical conductivity measurement; minerals; paper; partial discharges; power transformer insulation; transformer oil; PD; artificially contaminated mineral oil; copper sulphide contamination; corrosive sulphur effect; electrical conductivity measurement; oil impregnated paper; partial discharge; temperature 140 degC; thermal ageing; transformer insulation; Aging; Conductivity; Copper; Oil insulation; Partial discharges; Pollution measurement; Temperature measurement; Corrosive Sulphur; Oil; Partial Discharges; Transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering and Renewable Energy (ICPERE), 2014 International Conference on
  • Type

    conf

  • DOI
    10.1109/ICPERE.2014.7067200
  • Filename
    7067200