Title :
Verification of a Synchronous Machine Model for Stator Ground Fault Simulation Through Measurements in a Large Generator
Author :
Bermejo, A. ; Platero, C.A. ; Blazquez, F. ; Blanquez, F. ; Rebollo, E.
Author_Institution :
ETSII Electr. Eng. Dept., Polytech. Univ. of Madrid, Madrid, Spain
fYear :
2014
Firstpage :
240
Lastpage :
245
Abstract :
This paper presents a synchronous machine model designed to simulate internal ground faults along the stator windings. The purpose of this model is to help to set the 100 % stator ground fault protection based on the measurement of the third harmonic in the grounding resistor. The setting of the above protection is not easy, as the third harmonic in the generator depends on the operation point and the saturation of the machine. The main contribution of this paper is that the model has been validated through the measurements on a 106 MVA hydro-generator under no-faulty condition obtaining good results. The model has been also tested under faulty conditions obtaining coherent results.
Keywords :
fault simulation; hydroelectric generators; machine protection; stators; synchronous generators; grounding resistor; hydrogenerator; internal ground faults simulation; no-faulty condition; stator ground fault protection; stator ground fault simulation; stator windings; synchronous machine model verification; third harmonic measurement; Circuit faults; Generators; Harmonic analysis; Relays; Stator windings; Voltage measurement; Windings; component; Stator ground fault; power generation protection; stator ground fault protection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Artificial Intelligence, Modelling and Simulation (AIMS), 2014 2nd International Conference on
Print_ISBN :
978-1-4799-7599-0
Type :
conf
DOI :
10.1109/AIMS.2014.68
Filename :
7102467
Link To Document :
بازگشت