DocumentCode
3589090
Title
Initialization of DFIG based wind generating system
Author
Amutha, N. ; Kumar, B. Kalyan
Author_Institution
Electr. Eng. Dept., Indian Inst. of Technol. Madras, Chennai, India
fYear
2014
Firstpage
1
Lastpage
5
Abstract
Doubly fed induction generator (DFIG) has to be properly initialized for performing dynamic analysis. Even though DFIG has independent real and reactive power control, the real and reactive power output of DFIG depends both on the machine side parameters like wind speed and slip and network side parameters like grid voltage etc. This paper proposes a method for obtaining power flow solution incorporating DFIG based wind generation with only four variables as unknown variables as compared to other literature where more number of unknown variables are considered for solving the power flow including the DFIG. The simulation results of the proposed method for IEEE 14-bus system are presented.
Keywords
IEEE standards; asynchronous generators; load flow; reactive power control; wind power plants; DFIG based wind generating system; IEEE 14-bus system; doubly fed induction generator; power flow; reactive power control; Induction generators; Mathematical model; Reactive power; Rotors; Stators; Steady-state; Wind speed; Doubly fed Induction Generator (DFIG); Newton-Raphson (NR) method; Power flow; Slip;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Systems Conference (NPSC), 2014 Eighteenth National
Type
conf
DOI
10.1109/NPSC.2014.7103814
Filename
7103814
Link To Document