• DocumentCode
    35912
  • Title

    New methods of DGA diagnosis using IEC TC 10 and related databases Part 1: application of gas-ratio combinations

  • Author

    Sung-wook Kim ; Sung-jik Kim ; Hwang-dong Seo ; Jae-ryong Jung ; Hang-jun Yang ; Duval, Michel

  • Author_Institution
    HYOSUNG Corp., Changwon, South Korea
  • Volume
    20
  • Issue
    2
  • fYear
    2013
  • fDate
    Apr-13
  • Firstpage
    685
  • Lastpage
    690
  • Abstract
    This paper proposes a new method of DGA diagnosis, using IEC TC 10 and related databases. We analyzed five gas components (hydrogen, methane, acetylene, ethylene and ethane), which are used for analysis in the standards, with 10 types of gas ratios, and came up with 6 types of gas ratios among them, that can classify faults. Then, we reorganized and analyzed the 6 gas ratios with 15 gas-ratio combinations. From the results, we can suggest a new diagnosis method using 3 gas-ratio combinations that are able to classify fault areas clearly.
  • Keywords
    IEC standards; electrical faults; fault diagnosis; power transformer insulation; transformer oil; DGA diagnosis; IEC TC 10; acetylene; database; dissolved gas analysis; ethane; ethylene; fault classification; gas component; gas-ratio combination application; hydrogen; methane; Databases; Hydrogen; IEC standards; Oil insulation; Partial discharges; Power transformers; DGA diagnosis; IEC TC 10; gas ratio; new method;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2013.6508773
  • Filename
    6508773