DocumentCode
3591463
Title
Islanding detection of interconnected grids based on synchrophasor measurements (PMU)
Author
Mukhopadhyay, Pritwish ; Patil, Sunil ; Rajkumar, A. ; Chitturi, Srinivas ; Kumar, Chandan ; Jain, Ayush ; Gupta, Somesh
Author_Institution
WRLDC, POSOCO, Mumbai, India
fYear
2014
Firstpage
1
Lastpage
6
Abstract
This paper deals with the development of algorithm for islanding detection of Interconnected Grids as a result of Loss of interconnecting transmission line(s). The algorithm must also be able to segregate between the cases of islanding and cases of Loss of Parallel Feeder (LOPF), Generation Trip, and Load Trip. The new method uses 3 phase synchronized measurements obtained from Phasor Measurement Units (PMUs) for the detection of unbalanced islanding of Interconnected Grids. The model developed is simulated on two Area - two machine System in SIMULINK Environment. Furthermore, the algorithm is verified and tested on actual case study for the loss of the synchronization between NEW and SR grid of India.
Keywords
distributed power generation; phasor measurement; 3 phase synchronized measurements; LOPF; PMU; SIMULINK environment; generation trip; interconnected grids; interconnecting transmission line loss; islanding detection; load trip; parallel feeder loss; phasor measurement units; synchrophasor measurements; two area-two machine system; unbalanced islanding; Frequency synchronization; Generators; Islanding; Load modeling; Phasor measurement units; Synchronization; Islanding; Phasor data concentrator; Synchronization; Synchrophasor Measurement; WAMS(Wide Area Measurement System);
fLanguage
English
Publisher
ieee
Conference_Titel
Power India International Conference (PIICON), 2014 6th IEEE
Print_ISBN
978-1-4799-6041-5
Type
conf
DOI
10.1109/34084POWERI.2014.7117682
Filename
7117682
Link To Document