DocumentCode
3591593
Title
Impact of load models on distribution system performance and impact of D-STATCOM
Author
Deepmala ; Kumar, Ashwani
Author_Institution
Dept. of Electr. Eng., NIT Kurukshetra, Kurukshetra, India
fYear
2014
Firstpage
1
Lastpage
6
Abstract
This paper presents the modelling of D-STATCOM for radial distribution system. The device is used to compensate the node voltage to 1 p.u and its effect is studied on constant power (CP) and generic ZIP model. With the device placement at each node real power, reactive power, size of reactive compensation and percent rate of under voltage mitigated nodes are calculated. The best location of the device is decided on the basis of power loss reduction and percent rate of under voltage mitigated nodes (RUVMN) separately. The effect of summer load variation on the D_STATCOM placement is also presented in this paper.
Keywords
distribution networks; reactive power; static VAr compensators; D-STATCOM; constant power; distribution system performance; generic ZIP model; load models; power loss reduction; reactive power; real power; Automatic voltage control; Load flow; Load management; Load modeling; Mathematical model; Reactive power; Substations; D-STATCOM; Radial Distribution System (RDS) Rate of Under Voltage Mitigated Nodes (RUVMN); Static Load Models;
fLanguage
English
Publisher
ieee
Conference_Titel
Power India International Conference (PIICON), 2014 6th IEEE
Print_ISBN
978-1-4799-6041-5
Type
conf
DOI
10.1109/34084POWERI.2014.7117777