• DocumentCode
    3591628
  • Title

    Sensitivity of acoustic PD detection in GIS. Laboratory experiments and on-site experience

  • Author

    Schlemper, H.-D. ; Feser, K. ; Blaum, H. ; Kirchesch, P.

  • Author_Institution
    Inst. of Power Transmission & High Voltage Technol., Stuttgart Univ., Germany
  • Volume
    1
  • fYear
    1996
  • Firstpage
    99
  • Abstract
    The paper reports on acoustic partial discharge detection in the ultrasonic range for the onsite testing of GIS installations. Laboratory experiments demonstrate sensitivities comparable to sensitive electrical PD measuring methods. More than 1,500 gas compartments of GIS installations were checked during commissioning tests. A test procedure was developed. The onsite experience motivated the development of an automatic signal classification system
  • Keywords
    automatic testing; commissioning; electric breakdown; gas insulated substations; insulation testing; partial discharges; ultrasonic materials testing; GIS; acoustic partial discharge detection; automatic signal classification system; commissioning test procedure; gas compartments; insulation breakdown tests; laboratory experiments; onsite experiences; substations; test automation; ultrasonic testing; Acoustic measurements; Acoustic signal detection; Acoustic testing; Electric variables measurement; Geographic Information Systems; Laboratories; Partial discharge measurement; Partial discharges; Pattern classification; Ultrasonic variables measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-3531-7
  • Type

    conf

  • DOI
    10.1109/ELINSL.1996.549292
  • Filename
    549292