Abstract :
This paper presents the modification of under-voltage relays to trip tie lines of an industrial customer when a new cogeneration unit and two main transformers are installed. First, system configuration and operation condition of the cogeneration facility are introduced. To examine the dynamic responses of the cogeneration system during the fault contingencies, the mathematical models of the cogeneration units, excitation systems, governor systems and loads are included in the computer simulation. The under-voltage relays are designed according to the critical clearing time of the cogeneration units. To verify the effectiveness of the proposed protective scheme, the transient stability analysis of the industrial power system under various fault contingencies are performed. It is concluded that the proposed under-voltage relay settings can be accurately used as a backup protective strategy and the dynamic response of the isolated cogeneration system can be significantly enhanced.
Keywords :
cogeneration; power generation faults; power generation protection; power system transient stability; relays; backup protective strategy; cogeneration plant upgrade; cogeneration system; cogeneration unit; excitation system; protective scheme; tie-line; transient stability analysis; under-voltage relay; under-voltage relay setting; Cogeneration; Computer simulation; Electrical equipment industry; Mathematical model; Power system protection; Power system relaying; Power system transients; Protective relaying; Relays; Transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
TENCON 2004. 2004 IEEE Region 10 Conference
Print_ISBN :
0-7803-8560-8
Type :
conf
DOI :
10.1109/TENCON.2004.1414757
Filename :
1414757
Link To Document :
بازگشت