DocumentCode
3595100
Title
Improving the lightning performance of overhead distribution lines
Author
Thanasaksiri, Thanaphong
Author_Institution
Dept. of Electr. Eng., ChiangMai Univ., Thailand
fYear
2004
Firstpage
369
Abstract
Lightning performance of 22 kV overhead distribution lines has been investigated using lightning protection design workstation (LPDW). Shield wire and surge arresters play a significant role for protecting overhead distribution lines. The line with shield wire can reduce the number of flashovers in open ground and number of flashovers with nearby objects. The application of surge arresters provides better performance than shield wire, improving the lightning performance by installing surge arresters at every pole provides the best protection. The affects of footing impedance and also shield wire size have been analyzed.
Keywords
arresters; cable shielding; flashover; lightning protection; power distribution lines; power engineering computing; power overhead lines; 22 kV; flashovers; lightning performance; lightning protection design workstation; overhead distribution lines protection; shield wire; surge arresters; Arresters; Conductors; Flashover; Impedance; Insulation; Lightning protection; Power distribution lines; Surge protection; Voltage; Wire;