Title :
Experimental investigation on air breakdown under lightning impulses with various electrode configurations
Author :
Kamarudin, M.S. ; Radzi, N.H. ; Zulkifli, S.A. ; Abd-Rahman, R.
Author_Institution :
Dept. of Electr. Power Eng., Univ. Tun Hussein Onn, Malaysia
Abstract :
This paper describes sparkover characteristics of air. Standard lightning impulse of 1.2/50 is used in this study, along with three different electrode configurations. It is found that U50 and Emax increase with air pressure, particularly in larger gap lengths, with tests being carried out up to 0.25 MPa (abs). It is also found that higher gap lengths provide higher U50 and Emax for a given electrode configuration. A non-uniform field configuration provides very high electric field upon breakdown, whereas a more uniform field configuration provides higher breakdown voltage level.
Keywords :
electric breakdown; electric fields; lightning protection; air breakdown; air pressure; breakdown voltage level; electrode configurations; gap lengths; lightning protection; nonuniform field configuration; standard lightning impulse; uniform field configuration; very high electric field; Air breakdown; Electric field; Electrode configuration; Field utilization factor; Lightning;
Conference_Titel :
Clean Energy and Technology (CEAT) 2014, 3rd IET International Conference on
Print_ISBN :
978-1-78561-069-1
DOI :
10.1049/cp.2014.1502