• DocumentCode
    3597430
  • Title

    Parametric Evaluation of AC Losses in 500 MVA/1.1 kA High Temperature Superconducting (HTS) Cable for Efficient Power Transmission: Self Field Analysis

  • Author

    Vyas, Gaurav ; Dondapati, Raja Sekhar ; Usurumarti, Preeti Rao

  • Author_Institution
    Sch. of Mech. Eng., Lovely Prof. Univ., Phagwara, India
  • fYear
    2014
  • Firstpage
    315
  • Lastpage
    319
  • Abstract
    High Temperature Superconducting (HTS) cables are used for efficient power transmission. In the present work, AC losses in High Temperature superconducting cable due to self field with various parameters are calculated and validated with the published results. A 500 MVA / 1.1 kArms HTS transmission cable operating at 50 Hz is considered for the AC loss (self field) calculations. The major AC losses arise due to self field in the HTS cable and can be obtained by the approximated Norris equation. Two different superconducting cables, one with BSCCO and the other with YBCO tapes are considered for the present analysis. For a transport current of 1.1 kArms, the analytically calculated self field loss is 0.4 W/m (with BSCCO tape) and 0.5 W/m (with YBCO tape) respectively are comaprable with published experimental results.
  • Keywords
    power transmission lines; superconducting cables; AC loss parametric evaluation; HTS transmission cable; Norris equation approximation; apparent power 500 MVA; current 1.1 kA; high temperature superconducting cable; power transmission efficiency; self field analysis; Critical current density (superconductivity); Loss measurement; Power cables; Propagation losses; Superconducting cables; Yttrium barium copper oxide; AC loss; HTS cables; Self field;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Modelling Symposium (EMS), 2014 European
  • Print_ISBN
    978-1-4799-7411-5
  • Type

    conf

  • DOI
    10.1109/EMS.2014.95
  • Filename
    7154018