Title :
Research on the diagnosis of MV power cable insulation based on PD and VLF-Tanδ
Author :
Fan Yang ; Xiang Feng ; Ling Ruan ; Junwu Chen
Author_Institution :
State Grid Hubei Electr. Power Res. Inst., Wuhan, China
Abstract :
Reliability of power cable insulation is the key to the security of power system. In this paper, A comprehensive method for the diagnosis on insulation condition of distribution Cross Linked Polyethylene cable is presented, which including on-line and off-line Partial Discharge test and Very Low Frequency dielectric dissipation factor test. The Level in addition to the location of Partial Discharge and the assessment for condition of cable can be done by respectively using Partial Discharge and Very Low Frequency dielectric dissipation factor test. Experimental results have proved that this method is useful to assess the condition of Cross Linked Polyethylene cable.
Keywords :
insulation testing; partial discharges; polyethylene insulation; power cable insulation; power cable testing; MV power cable insulation; distribution cross linked polyethylene cable; insulation condition diagnosis; partial discharge test; power system security; very low frequency dielectric dissipation factor test; Joints; Partial discharges; Power cable insulation; Power cables; Trees - insulation; Voltage measurement; Partial Discharge; VLF-Tanδ; XLPE Cable;
Conference_Titel :
Electrical, Electronics and System Engineering (ICEESE), 2014 International Conference on
DOI :
10.1109/ICEESE.2014.7154568