Abstract :
This paper presents a new single-event characteristic, sag severity index (SSI), derived with respect to equipment sensitivity to voltage sags. It is more inclusive of associated uncertainties/variation in equipment response to voltage sags than existing single-event characteristics. By changing parameter settings, the index appropriately accounts for sag duration and adequately addresses the variation in equipment sensitivity. The value of the index changes continuously at the joining regions of different sag severity levels and reflects realistically the sensitivity trend of equipment embedded in voltage tolerance curves. The properties of the SSI are analyzed and discussed through comparison with characteristics of five previously reported single-event indices including four numerical indices and one fuzzy voltage sag index.
Keywords :
power apparatus; power supply quality; SSI; equipment sensitivity; power network; sag duration; sag severity index development; sag severity levels; single-event characterization; voltage sags; voltage tolerance curves; weak area identification; Color; Indexes; Joints; Power quality; Sensitivity; Standards; Voltage fluctuations; Equipment susceptibility; sag severity index (SSI); voltage sags; voltage tolerance curves;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2014.2362965
Filename :
6930764
Link To Document :
بازگشت