DocumentCode
3600951
Title
Interaction Between Interconnected and Isolated Grounding Systems: A Case Study of Transferred Potentials
Author
Faleiro, E. ; Pazos, F.J. ; Asensio, G. ; Denche, G. ; Garcia, D. ; Moreno, J.
Author_Institution
Dept. of Appl. Phys., Univ. Politec. de Madrid, Madrid, Spain
Volume
30
Issue
5
fYear
2015
Firstpage
2260
Lastpage
2267
Abstract
The effect caused by ground fault current in a complex system of interacting electrodes is theoretically studied. The calculation applies to a specific case in which a set of interconnected electrodes, which are part of a grounding facility network, are activated by ground fault current. Transferred potentials to adjacent passive electrodes are calculated and the most relevant parameters of the electrode system are evaluated. Finally, the convenience of connecting the grounding electrodes is discussed.
Keywords
earthing; power system faults; ground fault current; grounding electrodes; grounding facility network; interacting electrodes; interconnected electrodes; interconnected-isolated grounding system interaction; transferred potentials; Conductors; Electric potential; Electrodes; Equations; Fault currents; Grounding; Mathematical model; Earth fault; grounding analysis; method of moments; thin-wire structures; transferred potentials;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2014.2379434
Filename
6981980