DocumentCode :
3601539
Title :
The Feasibility of Cable Sheath Fault Detection by Monitoring Sheath-to-Ground Currents at the Ends of Cross-Bonding Sections
Author :
Marzinotto, Massimo ; Mazzanti, Giovanni
Author_Institution :
TERNA, Rome, Italy
Volume :
51
Issue :
6
fYear :
2015
Firstpage :
5376
Lastpage :
5384
Abstract :
This paper aims at checking the possibility that cable sheath faults in unipolar three-phase HV and extra HV cables with sheath cross-bonding systems can be detected by monitoring sheath-to-ground currents at the solid bonding ends of major cross-bonding sections. This goal is achieved by calculating such currents for some reference case studies of faults of the outer thermoplastic jacket in unipolar three-phase land cables for power transmission in flat formation. The case studies differ as to cable voltage ratings, resistance and location of the fault, symmetry of minor sections, and number of major sections. The results show that the aforementioned possibility does exist, particularly for some fault types and for sufficiently high cable load.
Keywords :
cable sheathing; earthing; fault diagnosis; power cables; cable sheath fault detection; cross-bonding sections; extra HV cables; power transmission; sheath-to-ground currents; solid bonding ends; thermoplastic jacket; unipolar three-phase HV cables; Bonding; Cable shielding; Grounding; Power cables; Resistance; Solids; Underwater cables; Bonding; Fault currents; Fault location; Grounding; Power cable installation; Power cable protective covering; fault currents; fault location; grounding; power cable installation; power cable protective covering;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.2015.2409802
Filename :
7056471
Link To Document :