• DocumentCode
    3601923
  • Title

    Experimental and Numerical Study of Division Factors of Fault Current and Measuring Current Due to Ground Wires of Transmission Lines

  • Author

    Bo Zhang ; Yukuan Jiang ; Jinliang He ; Qian Li

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • Volume
    51
  • Issue
    6
  • fYear
    2015
  • Firstpage
    4978
  • Lastpage
    4986
  • Abstract
    Due to the shunting action of the overhead ground wires of transmission lines or the neutral conductors connected to substation grounding, evaluating the ground wire division factors is a key step while designing the substation ground system or measuring the grounding resistance. In this paper, the principle and calculation models of the fault current division factor and the measuring current division factor are analyzed. The distinctions and relations of the two division factors are discussed. A method to evaluate the fault current division factor based on the measuring current division factor is put forward. Both the fault current division factor and the measuring current division factor are measured in a 220-/110-kV substation. The simulation results are in good agreement with the measured ones.
  • Keywords
    fault currents; power overhead lines; substations; wires (electric); fault current division factor; neutral conductors; overhead ground wires; substation; transmission lines; voltage 110 kV; voltage 220 kV; Current measurement; Fault currents; Grounding; Power transmission lines; Substations; Transmission line measurements; Wires; Current measurement; fault currents; grounding; impedance measurement; substations;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2015.2424866
  • Filename
    7089240