DocumentCode :
3608186
Title :
Research on lightning surge overvoltage of convertor station with 500 kV hot-standby circuit breakers
Author :
Youping Fan ; Lihui Wu ; Huimin Qiu ; Wu Wen ; Songkai Liu ; Hai Qian ; Dong Chen
Author_Institution :
Sch. of Electr. Eng., Wuhan Univ., Wuhan, China
Volume :
9
Issue :
7
fYear :
2015
Firstpage :
900
Lastpage :
907
Abstract :
This study introduces a circuit breaker flashover accident caused by lightning strokes in a row of Xingren convertor station in Guizhou. To find out the reason of the flashover and whether fault circuit breaker insulation coordination can meet requirements under multiple lightning strikes, the overvoltage condition of hot-standby circuit breakers under lightning surge is calculated and checked by using EMTP and full-scale high impulse voltage test of the fault circuit breaker is conducted for the first time. Owing to the hot-standby state of the circuit breaker, the flashover accident is more likely to happen when lightning surge invades the substation or convertor station again. Measures to improve the hot-standby circuit breakers´ lightning withstand level are proposed and by simulating analysis, the measure combined installing a line arrester at a tower of the inlet line and installing an arrester near a certain breaker on the line proves to be effective.
Keywords :
circuit breakers; lightning; overvoltage; standby generators; EMTP; circuit breaker flashover accident; convertor station; fault circuit breaker insulation coordination; full-scale high impulse voltage test; hot-standby circuit breakers; lightning strokes; lightning surge overvoltage; voltage 500 kV;
fLanguage :
English
Journal_Title :
Science, Measurement Technology, IET
Publisher :
iet
ISSN :
1751-8822
Type :
jour
DOI :
10.1049/iet-smt.2014.0243
Filename :
7296733
Link To Document :
بازگشت