DocumentCode :
3608190
Title :
Hybrid method on signal de-noising and representation for online partial discharge monitoring of power transformers at substations
Author :
Chan, Jeffery C. ; Hui Ma ; Saha, Tapan K.
Author_Institution :
Sch. of Inf. Technol. & Electr. Eng., Univ. of Queensland, Brisbane, QLD, Australia
Volume :
9
Issue :
7
fYear :
2015
Firstpage :
890
Lastpage :
899
Abstract :
To ensure reliable operations of power transformers, online condition monitoring needs to be performed. However, extensive noise can be coupled into measured signals and cause ambiguities in evaluating transformers´ conditions. This study proposes a hybrid method, which combines pre-whitening and blind equalisation for de-noising the signals obtained from online partial discharge (PD) measurements of transformers. A measured signal is first gone through a pre-whitening process for initial noise reduction and then processed by blind equalisation. Finally, an equalised signal that can reveal PD source in a transformer is converted to a kurtogram for an accurate PD pattern representation. The proposed method has been applied to signals obtained from laboratory experiments and online measurements of transformers at substations. Results show that the method can effectively de-noise PD signals contaminated by severe noise and consistently represent PD patterns induced by different PD sources.
Keywords :
blind equalisers; noise abatement; partial discharge measurement; power transformers; signal denoising; substations; white noise; PD measurement; blind equalisation; kurtogram; noise reduction; online condition monitoring; online partial discharge monitoring; power transformer; pre-whitening process; signal denoising; signal measurement; substation;
fLanguage :
English
Journal_Title :
Science, Measurement Technology, IET
Publisher :
iet
ISSN :
1751-8822
Type :
jour
DOI :
10.1049/iet-smt.2014.0358
Filename :
7296737
Link To Document :
بازگشت