DocumentCode
3608190
Title
Hybrid method on signal de-noising and representation for online partial discharge monitoring of power transformers at substations
Author
Chan, Jeffery C. ; Hui Ma ; Saha, Tapan K.
Author_Institution
Sch. of Inf. Technol. & Electr. Eng., Univ. of Queensland, Brisbane, QLD, Australia
Volume
9
Issue
7
fYear
2015
Firstpage
890
Lastpage
899
Abstract
To ensure reliable operations of power transformers, online condition monitoring needs to be performed. However, extensive noise can be coupled into measured signals and cause ambiguities in evaluating transformers´ conditions. This study proposes a hybrid method, which combines pre-whitening and blind equalisation for de-noising the signals obtained from online partial discharge (PD) measurements of transformers. A measured signal is first gone through a pre-whitening process for initial noise reduction and then processed by blind equalisation. Finally, an equalised signal that can reveal PD source in a transformer is converted to a kurtogram for an accurate PD pattern representation. The proposed method has been applied to signals obtained from laboratory experiments and online measurements of transformers at substations. Results show that the method can effectively de-noise PD signals contaminated by severe noise and consistently represent PD patterns induced by different PD sources.
Keywords
blind equalisers; noise abatement; partial discharge measurement; power transformers; signal denoising; substations; white noise; PD measurement; blind equalisation; kurtogram; noise reduction; online condition monitoring; online partial discharge monitoring; power transformer; pre-whitening process; signal denoising; signal measurement; substation;
fLanguage
English
Journal_Title
Science, Measurement Technology, IET
Publisher
iet
ISSN
1751-8822
Type
jour
DOI
10.1049/iet-smt.2014.0358
Filename
7296737
Link To Document