DocumentCode :
3608586
Title :
Electric field energy harvesting for on-line condition-monitoring device installed on high-voltage transmission tower
Author :
Dongsheng Zhao ; Dong Dai ; Licheng Li
Author_Institution :
Sch. of Electr. Power, South China Univ. of Technol., Guangzhou, China
Volume :
51
Issue :
21
fYear :
2015
Firstpage :
1692
Lastpage :
1693
Abstract :
A method for powering an on-line condition-monitoring device installed on a high-voltage transmission tower is presented. The technique uses the harvesting plate and a transformer both installed away from the transmission line to harvest the electric field energy. The circuit model of the method is analysed and the power equation given. The method has been experimentally validated. When the stray capacitance is 40 pF, about 645 mW was obtained with the load resistance 0.9 kΩ once 50 kV AC was applied on the electric field generator.
Keywords :
condition monitoring; electric fields; energy harvesting; poles and towers; power system measurement; power transformers; capacitance 40 pF; circuit model; electric field energy harvesting; electric field generator; harvesting plate; high-voltage transmission tower; online condition-monitoring device; power equation; resistance 0.9 kohm; transformer; transmission line; voltage 50 kV;
fLanguage :
English
Journal_Title :
Electronics Letters
Publisher :
iet
ISSN :
0013-5194
Type :
jour
DOI :
10.1049/el.2015.1975
Filename :
7300489
Link To Document :
بازگشت