DocumentCode
3608791
Title
Earth fault location based on evaluation of voltage sag at secondary side of medium voltage/low voltage transformers
Author
Topolanek, David ; Lehtonen, Matti ; Adzman, Mohd Rafi ; Toman, Petr
Author_Institution
Fac. of Electr. Eng. & Commun., Brno Univ. of Technol., Brno, Czech Republic
Volume
9
Issue
14
fYear
2015
Firstpage
2069
Lastpage
2077
Abstract
The main reasons for installation of power quality meters in distribution transformer substations are power quality monitoring and global evolution of electrical network towards the `smart grid´. In case that all measurements from the meters are properly synchronised and centralised, new possibilities of control or evaluation of the network are enabled. This contribution proposes the possibility for an earth fault localisation with the aid of synchronised data recorded on the low-voltage side of the medium voltage/low voltage transformers in compensated neutral distribution networks which are equipped with auxiliary resistor for short-time increasing of the active part of the fault current. The described method uses voltage sags evoked by connecting of the auxiliary resistor for locating the faulty section. The proposed method is tested with the help of numerical model which presents a part of the distribution network.
Keywords
earthing; fault location; power meters; power supply quality; power transformers; smart power grids; synchronisation; transformer substations; auxiliary resistor; compensated neutral distribution networks; distribution transformer substations; earth fault localisation; electrical network global evolution; fault current; medium voltage-low voltage transformers; numerical model; power quality meters; power quality monitoring; secondary side transformers; smart grid; voltage sag evaluation;
fLanguage
English
Journal_Title
Generation, Transmission Distribution, IET
Publisher
iet
ISSN
1751-8687
Type
jour
DOI
10.1049/iet-gtd.2014.0460
Filename
7302694
Link To Document