    Depolarization index for dielectric aging indicator of rotating machines

  • Author

    Bhumiwat, Supatra A.

  • Volume
    22
  • Issue
    6
  • fYear
    2015
  • fDate
    12/1/2015 12:00:00 AM
  • Firstpage
    3126
  • Lastpage
    3132
  • Abstract
    The term Depolarization Index (dP.I.) for rotating machines is introduced in this article as an additional information to the time-domain and frequency-domain dielectric response results for gaining high-precision interpretation and identification of some types of aging in solid dielectrics, particularly the non-restoring thermal trouble and insulation abrasion. Factors affecting the correctness and accuracy of dP.I. are discussed. The dP.I data from 60 medium-to-large generators and 117 large industrial motors, in Asia-Pacific were analyzed to provide the conclusion.
  • Keywords
    abrasion; ageing; electric generators; electric motors; frequency-domain analysis; machine insulation; time-domain analysis; Asia-Pacific; depolarization index; dielectric aging indicator; frequency-domain dielectric response; high-precision interpretation; industrial motors; insulation abrasion; medium-to-large generators; rotating machines; solid dielectric aging; time-domain dielectric response; Aging; Capacitance; Dielectrics; Indexes; Insulation; Rotating machines; Shape; Polarization; abrasion; absorption; capacitance; conduction; depolarization; dielectric; generators; motors; overheating;