• DocumentCode
    3612696
  • Title

    High voltage insulation properties of HFO1234ze

  • Author

    Koch, M. ; Franck, C.M.

  • Author_Institution
    Power Syst. & High Voltage Labs., ETH Zurich, Zurich, Switzerland
  • Volume
    22
  • Issue
    6
  • fYear
    2015
  • fDate
    12/1/2015 12:00:00 AM
  • Firstpage
    3260
  • Lastpage
    3268
  • Abstract
    Recently it was shown that it is possible to predict the breakdown voltages of arbitrary electrode configurations under standard voltage applications for electron attaching gases with a stepped leader model originally proposed for SF6. In this contribution this model was applied to the hydrofluoroolefin HFO1234ze. The parameters, which are necessary for the modeling, are derived from measurement of statistical and formative time lags in an electrode configuration with a homogeneous background field with a small protrusion. The parameters are used to predict the breakdown voltage for technical relevant geometries and standard voltage wave shapes. To verify these predictions, breakdown experiments in nearly homogeneous and strongly inhomogeneous field configurations with AC and lightning impulse voltage application of both polarities were performed. The hydrofluoroolefin exhibits insulation properties which are quite similar to those of SF6. Therefore it could be considered as admixture for high voltage gaseous insulations or as replacement in medium voltage equipment. For applications using the pure gas the temperature and pressure range has to be limited to prevent liquefaction. The good match between the simulations and the experiments gives evidence that the model can be applied to a broad range of other novel electron attaching gases as well.
  • Keywords
    SF6 insulation; electric breakdown; electrodes; electron attachment; joining processes; lightning protection; liquefaction; AC impulse voltage application; HFO1234ze high voltage insulation properties; SF6; arbitrary electrode configuration breakdown voltage prediction; electron attaching gases; formative time lags; high voltage gaseous insulation; homogeneous background field; hydrofluoroolefin high voltage insulation properties; lightning impulse voltage application; liquefaction prevention; medium voltage equipment; small protrusion; statistical measurement; stepped leader model; Breakdown voltage; Electric breakdown; Electrodes; Gases; Hafnium compounds; Insulation; Voltage measurement; Gas insulation; dielectric breakdown; gas discharges; modeling;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2015.005118
  • Filename
    7367520