DocumentCode :
3616349
Title :
Analysis of the insulated power-grid transient behavior after faulted phase tripping
Author :
N. Berbic;A. Nuhanovic;V. Madzarevic
Author_Institution :
Fac. of Electr. Eng., Univ. of Tuzla, Bosnia-Herzegovina
Volume :
3
fYear :
2004
fDate :
6/26/1905 12:00:00 AM
Firstpage :
987
Abstract :
The common cases of a nonselective operation of the phase to ground fault protection in the insulated power grids, which utilize inductive sensors for a voltage unbalance indication, are explained by ferroresonant processes in voltage transformers of healthy drains. This paper deals with phase to ground faults simulations in a known grid, that provide information about possible nonselective phase to ground faults protection operation.
Keywords :
"Transient analysis","Power transformer insulation","Circuit faults","Power grids","Voltage transformers","Power transformers","Nonlinear equations","Differential equations","Equivalent circuits","Protection"
Publisher :
ieee
Conference_Titel :
Electrotechnical Conference, 2004. MELECON 2004. Proceedings of the 12th IEEE Mediterranean
Print_ISBN :
0-7803-8271-4
Type :
conf
DOI :
10.1109/MELCON.2004.1348219
Filename :
1348219
Link To Document :