• DocumentCode
    3621499
  • Title

    Condition Monitoring of Power Transformers Using Acoustic Signal Prony´s Analysis

  • Author

    F.A. Wegelin;R.S. Magalhaes;L.A.L. de Almeida;M. Fontana

  • Author_Institution
    Departamento de Engenharia Elé
  • Volume
    2
  • fYear
    2005
  • fDate
    6/27/1905 12:00:00 AM
  • Firstpage
    1384
  • Lastpage
    1387
  • Abstract
    On-load tap changers (OLTCs) are electromechanical devices used for voltage regulation on electrical networks. A noninvasive monitoring technique was developed using Prony´s method for condition assessment of on-load tap-changers using vibration analysis signals. The transient vibration signals emitted during a tap change are recorded and processed using Prony´s spectral analysis and standard pre-processing techniques. Traditional condition monitoring techniques exhibit a certain degree of complexity, which may be a serious drawback when designing portable low-cost maintenance equipment. In order to reduce this complexity, we introduce a new index based on Prony´s analysis. The proposed technique is presented and its diagnosis capabilities are evaluated using experimental results collected from field installed equipments during their maintenance inspection
  • Keywords
    "Condition monitoring","Power transformers","Signal analysis","Acoustic devices","Acoustic emission","On load tap changers","Electromechanical devices","Voltage control","Transient analysis","Signal processing"
  • Publisher
    ieee
  • Conference_Titel
    Instrumentation and Measurement Technology Conference, 2005. IMTC 2005. Proceedings of the IEEE
  • ISSN
    1091-5281
  • Print_ISBN
    0-7803-8879-8
  • Type

    conf

  • DOI
    10.1109/IMTC.2005.1604376
  • Filename
    1604376