DocumentCode
3622727
Title
An improved two-terminal numerical algorithm for fault location estimation considering shunt capacitance
Author
H.H. Kim;C.J. Lee;Z.M. Radojevic;J.B. Park;J.R. Shin
Author_Institution
Dept. of Electr. Eng., Kon-Kuk Univ., Seoul, South Korea
fYear
2006
fDate
6/28/1905 12:00:00 AM
Abstract
This paper presents a new two-terminal numerical algorithm for fault location estimation using the synchronized phasor in time-domain. The proposed algorithm is also based on the synchronized voltage and current phasor measured from the PMUs(phasor measurement units) installed at both ends of the transmission lines. In this paper the algorithm is given with-out shunt capacitance and with shunt capacitance using 11 -model and estimated using DFT(discrete Fourier transform) and the LES(least error squares method). The algorithm uses a very short data window and classification for real-time transmission line protection. To test the validity of the proposed algorithm, the electro-magnetic transient program (EMTP) and MATLAB is used
Keywords
"Fault location","Capacitance","Time domain analysis","Voltage","Current measurement","Transmission line measurements","Measurement units","Fourier transforms","Power system protection","Testing"
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2006. IEEE
Print_ISBN
1-4244-0493-2
Type
conf
DOI
10.1109/PES.2006.1709414
Filename
1709414
Link To Document