DocumentCode
3628378
Title
Direct current control of active power filter without filter current measurement
Author
David Nedeljkovic;Mitja Nemec;Klemen Drobnic;Vanja Ambrozic
Author_Institution
University of Ljubljana, Faculty of Electrical Engineering, Tr?a?ka cesta 25, SI-1000, (Slovenia)
fYear
2008
fDate
6/1/2008 12:00:00 AM
Firstpage
72
Lastpage
76
Abstract
The paper presents a three-phase parallel active power filter without filter current measurement. Only supply grid voltage sensors, filter capacitor voltage sensor and supply line current sensors are used to provide filterpsila proper operation, aiming to reduce reactive power and line current distortion, caused by a non-linear load. Due to filterpsilas inverter-like topology with known parameters in filter branch, the predictive direct current control (DCC) method has been successfully applied, thus obtaining good dynamic response, reducing the commutation frequency of the active power filterpsilas switches and consequently decreasing the filter branch losses.
Keywords
"Active filters","Power filters","Current measurement","Power harmonic filters","Voltage measurement","Capacitors","Artificial neural networks"
Publisher
ieee
Conference_Titel
Power Electronics, Electrical Drives, Automation and Motion, 2008. SPEEDAM 2008. International Symposium on
Print_ISBN
978-1-4244-1663-9
Type
conf
DOI
10.1109/SPEEDHAM.2008.4581257
Filename
4581257
Link To Document