Direct current control of active power filter without filter current measurement
Author :
David Nedeljkovic;Mitja Nemec;Klemen Drobnic;Vanja Ambrozic
Author_Institution :
University of Ljubljana, Faculty of Electrical Engineering, Tr?a?ka cesta 25, SI-1000, (Slovenia)
fYear :
2008
fDate :
6/1/2008 12:00:00 AM
Firstpage :
72
Lastpage :
76
Abstract :
The paper presents a three-phase parallel active power filter without filter current measurement. Only supply grid voltage sensors, filter capacitor voltage sensor and supply line current sensors are used to provide filterpsila proper operation, aiming to reduce reactive power and line current distortion, caused by a non-linear load. Due to filterpsilas inverter-like topology with known parameters in filter branch, the predictive direct current control (DCC) method has been successfully applied, thus obtaining good dynamic response, reducing the commutation frequency of the active power filterpsilas switches and consequently decreasing the filter branch losses.