Standard measurement of interharmonics in a power supply system while evaluating obnoxiousness of a flicker
Author :
Grzegorz Wiczynski
Author_Institution :
Institute of Electrical Engineering and Electronics, Pozna? University of Technology, Poland
fYear :
2008
Firstpage :
1
Lastpage :
4
Abstract :
Flicker is caused by the fluctuation of voltage that supplies the source of light. Such a fluctuations are accompanied by the existence of interharmonics. This paper summarizes the measurement of interharmonics accordant to IEC 61000-4-7 standard. Also included are the results of analysis of flickermeter signal chain for the input signal composed of two interharmonics. The relation between the Pst indicator value and amplitudes and phases of the two interharmonics is determined. Condition for taking into consideration the phase relations while evaluating the Pst indicator value is also given. It is concluded that the evaluation of Pst indicator value is not possible only on the basis of IEC 61000-4-7 standard measurements for harmonics.
Keywords :
"Measurement standards","Power measurement","Power supplies","Voltage fluctuations","IEC standards","Signal analysis","Power harmonic filters","Power quality","Frequency measurement","Graphics"