DocumentCode :
3637342
Title :
Experimental analysis of electrical values during earth faults
Author :
P. Toman;J. Dvořák;J. Orságová;S. Mišák
Author_Institution :
Brno University of Technology, Czech Republic
fYear :
2010
Firstpage :
185
Lastpage :
190
Abstract :
The MV compensated Networks in Czech Republic are operated as nonsymmetrical, that means as networks with non-transposed lines. The paper deals with experiments which were realized in distribution network held by E.ON Czech Republic. There were made a few different faults (low-impedance, spark gap arc, damaged MV cable, 1.6 kΩ, 4 kΩ and unearthed console of concrete tower) for three different places, for tuned and untuned Petersen coil and for some types of faults for all phases too, that means forty eight experimental faults. During each experiment the shunting of affected phase was applied.
Keywords :
"Earth","Microprocessors","Analytical models","Microcontrollers","Transient analysis","Fault tolerance","Hardware design languages","Information analysis","Information technology","Computer science"
Publisher :
ieee
Conference_Titel :
Electric Power Quality and Supply Reliability Conference (PQ), 2010
Print_ISBN :
978-1-4244-6978-9
Type :
conf
DOI :
10.1109/PQ.2010.5550000
Filename :
5550000
Link To Document :
بازگشت