• DocumentCode
    3640212
  • Title

    Separation of no-load losses for distribution transformers using experimental methods: Two frequencies and two temperatures

  • Author

    Juan C Olivares-Galván;Rafael Escarela-Pérez;Pavlos S Georgilakis;Eduardo Campero-Littlewood

  • Author_Institution
    Dept. de Energia, Univ. Autonoma Metropolitana- Azcapotzalco, Mexico City, Mexico
  • fYear
    2010
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper presents an investigation on the separation of no-load losses into hysteresis and eddy current losses. The two-temperatures and the two-frequency methods are used to separate the losses in a transformer core. Two measurements are required for the calculation of the eddy and hysteresis losses. The methodologies are applied to a commercial 15 kVA shell-type, single-phase distribution transformer, with core lamination thickness of 0.23 mm. The main contribution of this paper is the presentation of a practical and validated example for the accurate computation of eddy current losses and hysteresis losses in distribution transformers.
  • Publisher
    iet
  • Conference_Titel
    Power Generation, Transmission, Distribution and Energy Conversion (MedPower 2010), 7th Mediterranean Conference and Exhibition on
  • Type

    conf

  • DOI
    10.1049/cp.2010.0900
  • Filename
    5715978